3.2.30 VONK (Message Type V)
VONK Example SIA Mode Description
<LF><CRC><V><sequence#><receiver#><line#>[#aa|123456789ABCDEFG]<CR>
Table 90: VONK (Message Type V) Byte Description
Title Description
LF Standard line feed character.
CRC Cyclical redundancy check number.
Message Type V
sequence# The message sequence number. The valid sequence number range is 0001
to 9999.
receiver# The receiver gateway that sent the message. Valid digits: 01 to 99 for
D6600.
line#
(Line/Group #)
The line number of the line in the receiver gateway that sent the message.
Valid digits: 00 to 99. The receiver uses Line 0 (zero) for internal
messages.
account # The communicator's account number has two digits.
Data Status of zones 1 to 16. If the zone is closed, a “.(Period) appears in this
position. If the zone is open, any digit from 1 to G appears in this position.