Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication
Protocols
Bosch Security Systems | 2012.09 | 4998122703-05
3.2.3 Ademco 10-Digit (Message Type b)
10-Digit
Example
SIA Mode Description
<LF><CRC><a><sequence#><receiver#><line#>[#aaaaaaaaaa|58QXYZGGCCC]<CR>
Table 45: Ademco 10-Digit (Message Type b) Byte Description
Title Description
LF Standard line feed character.
CRC Cyclical redundancy check number.
a Message Type
Ademco Contact-ID.
sequence# The message sequence number. The valid sequence number range is 0001 to
9999.
receiver# The receiver gateway that sent the message. Valid digits are 01 to 99 for the
D6600/D6100/D6100IPv6.
line# The line number of the line in the Receiver/Gateway that sent the message.
Valid digits are: 00- 99. The D6600 uses line#0 for Receiver/Gateway
messages.
account# The communicator's account number.
58 Ademco Contact-ID format number for 10 digits account.
Q Qualifier, 1=New event or opening, 3=New restore or closing, 6=Previous event
XYZ Class code and event code (refer to Appendix A: Contact ID Event Code
Classifications)
GG Group number
CCC Zone codes or user ID
Figure 9: Message sent to printer
mm/ddshh:mmsLxxsCIDsACCTsaaaaaaaaaa
+++sNNNsEVENT=XYZsG=GGsC=CCC
For lines that are grouped, Gxx appears instead of Lxx.
Table 46: Ademco Contact-ID (Message Type a) Printer Output
Characters Description
CID
Contact-ID format.
Gxx Grouped Line numbers.
Lxx
Line number.
NNN
If Q = 1, print E/O for new event or opening If Q = 3, print R/C for restore or closing
If Q = 6, print “OLD” for old messages and events.
Kommentare zu diesen Handbüchern