47
3.2.4 Ademco 4-1 Express (Message Type b)
4-1 Express
Example
SIA Mode Description
<LF><CRC><b><sequence#><receiver#><line#>[#aaaa|X]<CR>
Table 47: Ademco 4-1 Express (Message Type b) Byte Description
Title Description
LF Standard line feed character.
CRC Cyclical redundancy check number.
Message Type b
sequence# The message sequence number. The valid sequence number range is
0001 to 9999.
receiver# The receiver gateway that sent the message. Valid digits are 01 to 99 for
the D6600/D6100/D6100IPv6.
line#
(Line/Group #)
The line number of the line in the receiver gateway that sent the
message. Valid digits are 00 to 99. The receiver uses Line 0 (zero) for
internal messages.
account# The communicator's account number has four digits.
X Zone number
Figure 10: Message sent to printer
mm/ddshh:mmsLxxsE41sACCTsaaaasEVENT=X
For lines that are grouped, Gxx appears instead
of Lxx.
Table 48: Ademco 4-1 Express (Message Type b) Printer Output
Characters Description
E41
Ademco 4-1 Express format.
Lxx:
Line number.
Gxx Grouped line numbers.