Conettix D6600 Bedienungsanleitung Seite 66

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 185
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 65
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication
Protocols
66
3.2.21 Seriee FSK (Message Type k)
Seriee FSK
Example
SIA Mode Description
<LF><CRC><k><sequence#><receiver#><line#>[#aaaaa|EZZ]<CR>
Table 77: Seriee FSK (Message Type k) Byte Description
Title Description
LF Standard line feed character.
CRC Cyclical redundancy check number.
Message Type k
sequence# The message sequence number. The valid sequence number range is 0001
to 9999.
receiver# The receiver gateway that sent the message. Valid digits are 01 to 99 for
D6600/D6100/D6100IPv6.
line#
(Line/Group #)
The line number of the line in the receiver gateway that sent the message.
Valid digits are 00 to 99. The receiver uses Line 0 (zero) for internal
messages.
Account # The communicator's account number has up to six digits.
E Event code.
ZZ Zone number.
Seitenansicht 65
1 2 ... 61 62 63 64 65 66 67 68 69 70 71 ... 184 185

Kommentare zu diesen Handbüchern

Keine Kommentare