Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication
Protocols
.
Bosch Security Systems, Inc. | 2012.09 | 4998122703-05
71
3.2.25 Silent Knight FSK2 (Message Type m)
Silent Knight
FSK2 Example
SIA Mode Description
<LF><CRC><m><sequence#><receiver#><line#>[#aaaaaa|
EEZZ”ECZZ”EEZZ”EEZZ”EEZZ”EEZZ”EEZZ”EEZZ]<CR>
Table 84: Silent Knight FSK2 (Message Type m) Byte Description
Title Description
LF Standard line feed character.
CRC Cyclical redundancy check number.
Message Type m
sequence# The message sequence number. The valid sequence number range is 0001
to 9999.
receiver# The receiver gateway that sent the message. Valid digits: 01 to 99 for
D6600/D6100/D6100IPv6.
line#
(Line/Group #)
The line number of the line in the receiver gateway that sent the message.
Valid digits: 00 to 99. The receiver uses Line 0 (zero) for internal messages.
account # The communicator's account number has up to six digits.
EEZZ”EEZZ”EEZZ”EEZ
Z”EEZZ”EEZZ”EEZZ”E
EZZ
Up to eight reports. One report has four digits: one-digit event code, one-
digit condition code, and two-digit zone code. The quote (“) is the
separation character.
3.2.26 Silent Knight FSK80 (Message Type <TAB>)
Silent Knight
FSK80
Example
SIA Mode Description
<LF><CRC><TAB><sequence#><receiver#><line#>[#AAAA|NBAXY]<CR>
Table 85: Silent Knight FSK80 (Message Type <TAB>) Byte Description
Title Description
LF Standard line feed character.
CRC Cyclical redundancy check number.
Message Type <TAB>
sequence# The message sequence number. The valid sequence number range is 0001
to 9999.
receiver# The receiver gateway that sent the message. Valid digits: 01 to 99 for
D6600/D6100/D6100IPv6.
line#
(Line/Group #)
The line number of the line in the receiver gateway that sent the message.
Valid digits: 00 to 99. The receiver uses Line 0 (zero) for internal messages.
account # The communicator's account number has four digits.
NBA Alarm event