3.2.14 ITI (Message Type I)
ITI Example SIA Mode Description
<LF><CRC><I><sequence#><receiver#><line#>[#aaaaa|GIZZEWN]<CR>
Table 67: ITI (Message Type I) Byte Description
Title Description
LF Standard line feed character.
CRC Cyclical redundancy check number.
Message Type I (Captial I).
sequence# The message sequence number. The valid sequence number range is 0001
to 9999.
receiver# The receiver gateway that sent the message. Valid digits are 01 to 99 for
the D6600/D6100/D6100IPv6.
line#
(Line/Group #)
The line number of the line in the receiver gateway that sent the message.
Valid digits are 00 to 99. The receiver uses Line 0 (zero) for internal
messages.
account# The communicator's account number has up to six digits.
G Group number.
I O/C User ID.
ZZ Zone number.
E Condition code.
W Protection level was.
N Protection level now.
3.2.15 Link Test (Message Type <TAB>)
Link Test
Example
SIA Mode Description
<LF><CRC><TAB><sequence#><receiver#> []<CR>
The D6600/D6100IPv6/D6100i can automatically generate this message at the preprogrammed
intervals.
Table 68: Link Test (Message Type <TAB>) Description
Title Description
LF Standard line feed character.
CRC Cyclical redundancy check number.
Message Type <TAB>
sequence# The message sequence number. The valid sequence number range is 0001
to 9999.
receiver# The receiver gateway that sent the message. Valid digits are 01 to 99 for
the D6600/D6100/D6100IPv6.